Doc Bong Hybrid >>

Eneftech Innovative Engineering Services

Online
Period: Sep 24 – Oct 23, 2026 Effective Rate: ₱11.90/kWh

BOHECO 1 Bill

₱16,898

1,420 kWh

₱11.90 all-in rate

Solar Yield (30d)

464.0 kWh

15.5 kWh/day

24.6% of total load

Clipped Solar

~716 kWh

60.7% Curtailed

Zero-Export clamp

UPS Reserve

100% Floor

18:00–03:00

Blackout Defense
Validated Outage Protection Strategy

Why Evening Loads Are Supplied from the Grid (18:00 – 03:00)

Inverter telemetry confirms the 16 kWh battery holds a dedicated 90%–100% reserve throughout the evening, discharging only between 03:00 AM – 06:00 AM down to 20% SOC. This safeguards the facility against Bohol's frequent grid failures. Once released at 03:00 AM, sunrise is only ~3 hours away to resume solar generation.

Logged Grid Failures (Inverter Carried Load):

Oct 4: 7.25h Blackout
Oct 17: 2.5h Blackout
Oct 24: 7.0h Blackout

24-Hour Power Dynamics & Curtailment

Average 5-min inverter telemetry

Solar PV Battery % Curtailed Grid Load
07:00 – 11:30 AM: Morning solar recharges battery after 03:00–06:00 AM cycle.
11:30 AM – 03:30 PM: Battery full. Inverter throttles solar from ~8 kW down to ~300 W.
18:00 – 03:00 AM: Battery held at 100% UPS reserve. Grid supplies ~4 kW.

Optimization Scenario Simulator

Adjust rates or tap presets to recalculate bills while retaining outage defense.

BOHECO 1 Tariff ₱11.90 / kWh
Export Credit Rate ₱6.49 / kWh
Battery Storage Added +32 kWh (48 total)
Scenario A: Net Metering Capex: ₱25k

BOHECO 1 Interconnection

Lifts zero-export clamp. Exports ~716 kWh/mo of surplus solar. 16 kWh battery stays 100% reserved for blackouts.

Monthly Bill: ₱12,252.93
Monthly Savings: ₱4,645.62 / mo
Payback Period: 5.4 Months
Zero battery wear & fastest payback
Scenario B: Storage Expansion Capex: ₱280k

Dedicated Night Battery (+32 kWh)

Expands storage to 48 kWh. 16 kWh is locked as UPS floor, while 32 kWh cycles 18:00–06:00 to eliminate evening grid load.

Monthly Bill: ₱7,440.91
Monthly Savings: ₱9,457.64 / mo
Payback Period: 2.46 Years
Maximum grid independence + dual UPS
Combined Synergy Capex: ₱305k

Net Metering + Storage (+32 kWh)

Cycles 32 kWh nightly, retains 16 kWh blackout reserve, and exports any residual midday solar overflow for grid credit.

Monthly Bill: ₱6,043.40
Monthly Savings: ₱10,855.15 / mo
Payback Period: 2.34 Years
Lowest bill & full generation utilization

5-Year Cumulative Cash Savings Projection

Implementation Roadmap

Phase 1 (Months 1–2) Immediate ROI

BOHECO 1 Net Metering Interconnection

  • Submit application for Net Metering Interconnection with BOHECO 1.
  • Complete Distribution Impact Study (DIS) & secure LGU CCEI permit.
  • Install approved bi-directional meter and disable Zero-Export clamp.
  • Outcome: Converts ~716 kWh/month of wasted solar into ~₱4,645/mo bill credits while keeping 100% emergency blackout reserve.
Phase 2 (Months 3–6) Long-term Autonomy

Dual-Module Storage Expansion (+32 kWh)

  • Install two 16 kWh 51.2V 314Ah LiFePO4 Dyness batteries in parallel.
  • Program Solis Hybrid Inverter with a locked 33% (16 kWh) non-discharging UPS floor.
  • Permit upper 67% (32 kWh) to discharge over the 18:00–06:00 evening peak.
  • Outcome: Drops monthly grid bill from ₱16,898 to ~₱7,440/mo with permanent 6+ hour backup capacity during blackouts.